TP11 Series Products
TP11 Series UPS is the single into a single company for the Chinese power grid OST technology environment and network systems for the power requirements of high reliability, designed for finance, communications, insurance, transport, taxation, military, security, energy, education, government, business Network computer rooms and small smart devices, precision instruments designed for high performance sine wave online UPS systems, and is particularly suitable for harsh power environments.
TP11 single into a single series of UPS China Power Grid environment design, will undoubtedly become the best partner to ensure network stability of the system, and can provide users with an isolation transformer, external chargers and adapters, and other optional SNMP.
TP11 Series Product Technical Specifications
◆single into a single 220V, suitable for Chinese power grid;
◆Wide AC input voltage range, reducing the frequency of use of the battery, effectively extending the battery life;
◆Wide input frequency range, to ensure access to a variety of fuel generators can be stable.
Highly reliable and stable operation of the design concept, protect network systems
◆Pure online double conversion topology architecture designed to provide the best power quality;
◆using SPWM pulse width modulation, IGBT power modules and output isolation transformer, ensure that the UPS output without interference from power fluctuations and noise;
◆the use of advanced technology and electronic lock-synchronous static bypass switch, output zero transfer time to meet the high standards of precision equipment for power supply requirements to ensure the continuity of load power;
◆advanced microprocessor-based control technology, to enhance the availability and reliability of the system.
Intelligent battery management technology to effectively delay the battery life
◆intelligent battery management technology, Equalize / Float automatic conversion, can effectively extend battery life;
◆can flow both parallel self-power charger, sharing imbalance ≤3%, effectively shortening the charging time, the maximum configuration of the system to meet the requirements.
Stability and reliability perfect protection functions, which greatly ensure system
◆have superior cold start capability, cold start operation in the case of full load, to meet the emergency needs of the user;
◆have intelligent unmanned capabilities to meet the needs of special occasions;
◆have power self-diagnostic function, the UPS can detect hidden faults, which may lead to a failure to avoid the risk of potential hazards;
◆with input surge surge protection; output overload / short circuit protection; battery failure and low voltage warning protection; battery overcharge protection; inverter over-temperature and failover bypass protection and other protection, to ensure the system is running stability and reliability.
Goodwill of the man-machine interface and network management capabilities, makes machine communication distance
◆have a variety of sound and light warning function, concise;
◆Large-screen LCD Chinese LCD interface to provide accurate UPS operating parameters and working conditions;
◆through RS232 interface, with smart UPS monitoring software can be used with a PC for instant messaging, various parameters and status of the UPS system at a glance display on the PC communication interface, by setting, the computer can perform a variety of functions for UPS systems direct control;
◆DB9 with RS485 interface and optional dry contact interface functions;
◆The external SNMP adapter, the system has a direct Internet access, providing instant messages UPS data and power through a variety of network management platform for communication, management, system instantly become a network.
TP11 Series Applications
small computer center, between networks, communications systems, automatic control systems and precision equipment, server farms, industrial process control applications, routers, switches, office automation, computer equipment, etc.
TP11 Series Model name defined
TP11 ***
TP11: said single into a single series
*: Indicates the UPS capacity, the unit is Kva
*: Indicates whether the built-in battery, with the S suffix indicates built-in battery, the series UPS only 6Kva the following capacity (including 6Kva) may be within
Set the battery.
Such as: TP1110 is expressed as a single time-lapse single out 10Kva host, TP1106S expressed as a single into a single built-in battery 6Kva standard machine.
TP11 Series Technical Specifications Table
Model |
TP1101 |
TP1102 |
TP1103 |
TP1104 |
TP1106 |
TP1108 |
TP1110 |
TP1115 |
TP1120 |
Capacity |
1KVA |
2KVA |
3KVA |
4KVA |
6KVA |
8KVA |
10KVA |
15KVA |
20KVA |
AC input | |||||||||
Voltage |
Single-phase 165 ~ 275VAC |
||||||||
Frequency |
50(60) Hz ±5% |
||||||||
Maximum current |
6A |
12A |
18A |
24A |
34A |
45A |
56A |
82A |
112A |
AC output | |||||||||
Voltage |
Single-phase 220VAC |
||||||||
Frequency |
50(60) Hz |
||||||||
Voltage stability |
±1% |
||||||||
Frequency Stability |
±0.5% (when mains power failure) |
||||||||
Waveform |
SPWM sine wave |
||||||||
Power factor |
0.8 (lagging) |
||||||||
Distortion |
<3% (linear load) |
||||||||
Transient response |
Voltage variation ≤4% (100% load into or cut out) |
||||||||
Output current crest factor |
3:1 (Max.) |
||||||||
Battery | |||||||||
Voltage |
48VDC |
192VDC |
|||||||
Type |
Maintenance-free lead-acid batteries |
||||||||
Charging time |
8-10 hours to complete 90% of capacity |
||||||||
Warning devices | |||||||||
Mains power |
The buzzer beeps once every 4 seconds |
||||||||
Mains abnormal |
The buzzer beeps once every four seconds, mains mode indicator flashes |
||||||||
The battery will run out |
The buzzer beeps once every second, the battery mode indicator flashes, battery low voltage lights |
||||||||
Overload |
Overload indicator light, buzzer sounding |
||||||||
UPS abnormal |
Malfunction indicator light, buzzer sounding |
||||||||
Internal protection | |||||||||
Battery |
Low battery automatic shutdown, automatic restart utility power is restored, miniature circuit breaker protection |
||||||||
Overload |
Go to bypass automatic overload (120-150%) after 60 seconds, after the resumption of normal load |
||||||||
Over Temperature |
UPS internal temperature> 85 ℃automatically go to bypass |
||||||||
Output short circuit |
Limiting, automatic shutdown, mini circuit breaker protection |
||||||||
UPS abnormal |
Automatically go to bypass the mains load |
||||||||
Clutter filter |
10 ~ 100KHz at 40dB; 100KHz ~ 100MHz at 70dB |
||||||||
Control Panel | |||||||||
LCD Display |
UPS operating status display, input, output voltage; input and output frequency; battery voltage; Output Power (%); inverter temperature |
||||||||
Low battery indicator |
When the battery voltage is low light |
||||||||
Overload indicator |
Overload light |
||||||||
Fault indicator |
Failure light |
||||||||
UPS status indicators |
AC mode; battery mode; inverter power supply; bypass supply; UPS abnormal |
||||||||
Safety standards | |||||||||
Safety |
GB4943 |
||||||||
EMI |
IEC62040-2,GB7260.2 |
||||||||
EMS |
IEC61000-4-2~5,GB/T 17626.2~5 |
||||||||
Environment | |||||||||
Temperature |
0~40℃ |
||||||||
Humidity |
20 ~ 90% non-condensing |
||||||||
Elevation |
Less than 1000m (above sea level for each additional 500m, UPS output derating 5%) |
||||||||
Noise |
<58dB (at 1 m from the box) |
||||||||
Appearance | |||||||||
Input and output wiring |
Terminal Blocks |
||||||||
Weight (without battery) Kg |
60 |
68 |
70 |
75 |
80 |
110 |
115 |
200 |
230 |
Dimensions W × D × H (mm) |
250×580×700 (Standard) 250×580×540 (Long-acting) |
250×580×700 |
310×590×850 |
410×680×1020 |
|||||
Other | |||||||||
Overall efficiency |
>85% |
||||||||
Mains power conversion time |
0ms |
||||||||
Communication Interface |
RS232 interface for direct external SNMP card; RS485, DB9 dry Node Optional |